Home » Shop » hot sale » Absolute Process Instruments APD 6380 _ AC to DC transmitter. Fully isolated

Absolute Process Instruments APD 6380 _ AC to DC transmitter. Fully isolated

Original price was: $375.20.Current price is: $213.20.

Sale!

40 in stock

SKU: APD 6380 Category:

Absolute Process Instruments APD 6380 _ AC to DC transmitter. Fully isolated

Cecomp Electronics, APD 6380, AC to DC Isolated Signal Conditioner, 18 Output Ranges, 85-265 VAC, 60-300 VDC Power

Features:

  • One Minute Setup for Hundreds of I/O Ranges
  • External Switches & Tables for Range Selection
  • Zero and Span Output Calibration Potentiometers
  • Full 1200 V Input/Output/Power Isolation
  • Input and Output LoopTracker® LEDs
  • Output Test Button
  • Built-In Loop Power Supply for Sink/Source Output

Applications:

  • Convert, Boost, and Rescale Process Signals
  • Isolate Single-Ended (Common Ground) PLC Inputs
  • Interface Process Signals with Panel Meters, PLCs, Recorders, Data Acquisition, DCS, & SCADA Systems

The APD 6380 accepts an AC voltage or current input and provides an optically isolated DC voltage or current output that is linearly related to the input.

Typical applications include signal isolation, conversion, boosting or a combination of the three. Full 3-way isolation (input, output, power) makes this module useful for ground loop elimination, common mode signal rejection or noise pickup reduction.

Sink/Source Output Versatility

For maximum versatility a milliamp output can be selectively wired for sinking or sourcing. This allows the APD 6380 milliamp output to connect to a powered or unpowered current loop. The 20 VDC output loop supply can be used to power a passive mA device if required.

LoopTracker

API exclusive features include two LoopTracker LEDs (green for input, red for output) that vary in intensity with changes in the process input and output signals. These provide a quick visual picture of your process loop at all times and can greatly aid in saving time during initial startup and/or troubleshooting.

Output Test

An API exclusive feature includes the test button to provide a fixed output (independent of the input) when held depressed. The test output level is potentiometer adjustable from 0 to 100% of output span. The output test button greatly aids in saving time during initial startup and/or troubleshooting

Specifications Table:

Input True RMS 0-40 mVAC to 0-300 VAC, 0-4 mAAC to 0-200 mAAC. Field configurable”specify range if factory is to set switches.
Output 0-1 V to 0-10 VDC, ±5 VDC, ±10 VDC, 0-2 mA to 20 mADC. Field configurable”specify range if factory is to set switches.
AC Input Range Factory configured, please specify input range. Consult factory for special ranges

  • Voltage: 0-40 mVAC to 0-300 VAC
  • Current: 0-4 mAAC to 0-200 mAAC

Measurements are true RMS

Input Impedance (Voltage Input)
  • Voltage (0-4 VAC): 1 MΩ minimum
  • Voltage (>4 VAC): 220 kΩ minimum
  • Current: 10 Ω typical
Input Frequency 40 Hz to 1000 Hz sinusoidal
Common Mode Rejection 120 dB minimum
DC Output Ranges Field selectable ranges via switch settings

  • VVoltage: 0-1 VDC to 0-10 VDC, 10 mA max
  • Bipolar voltage: ±1 VDC to ±10 VDC
  • Current: 0-2 mADC to 0-20 mADC, 20 V compliance, 1000 Ω at 20 mA
  • Output offset: ±100% in 15% increments
Output Calibration Multi-turn zero and span potentiometers (±15% of span adjustment range typical)
Output Loop Power Supply
  • 20 VDC nominal, regulated, 25 mADC
  • Max. ripple, less than 10 mVRMS

May be selectively wired for sinking or sourcing mA output

Output Test Front momentary button sets output to test level. Potentiometer adjustable 0-100% of span.
Output Ripple and Noise Less than 10 mVRMS ripple and noise
Linearity Better than ±0.1% of span
Ambient Temperature Range and Stability
  • “10°C to +60°C operating ambient
  • Better than ±0.02% of span per °C stability
Response Time 200 milliseconds nominal (0-90%)
Isolation
  • 1200 VRMS minimum
  • Full isolation: power to input, power to output, input to output
Housing
  • IP 40, requires installation in panel or enclosure
  • For use in Pollution Degree 2 Environment
  • Mount vertically to a 35 mm DIN rail
Connectors Four 4-terminal removable connectors, 14 AWG max wire size
Power 85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum